Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
69
Menu
Parameter
Description
Default Value
change the value.
HF hold period
Sets the period of the
compressor for running at the
high frequency after its
running frequency exceed this
high frequency.
60s
Max adjust step
Sets the maximum rotational
speed adjustment step for the
compressor.
60 rpm
Protection adjust
step
Sets the rotational speed
adjustment step for the
compressor under protection.
90 rpm
Suction &
discharge press
diff for startup
Sets the suction and discharge
pressure difference for normal
startup of the compressor.
You are not recommended to
change the value.
0.00 Mpa
Discharge HT for
freq rise limit
Sets the discharge temperature
for compressor frequency rise
limit.
105.0°C
Discharge HT for
freq fall
Sets the discharge temperature
for forcibly decreasing the
compressor frequency.
115.0°C
Discharge HT for
shutdown
Sets the discharge temperature
for shutting down the
compressor.
125.0°C
Discharge HP for
freq rise limit
Sets the discharge pressure for
compressor frequency rise
limit.
3.95 Mpa
Discharge HP for
freq fall
Sets the discharge pressure for
forcibly decreasing the
compressor frequency.
4.05 Mpa
Discharge HP for
shutdown
Sets the discharge pressure for
shutting down the compressor.
4.35 Mpa
Discharge LP for
freq fall limit
Sets the discharge pressure for
compressor frequency rise
limit.
1.80 Mpa
Discharge LP for
freq rise
Sets the discharge pressure for
forcibly increasing the
compressor frequency.
1.60 Mpa
Suction HP for
speed rise limit
Sets the suction pressure for
indoor fan
speed rise limit
.
1.65 Mpa