Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
62
Menu
Parameter
Description
Default Value
2 starts first. After the
cooling requirement
increases, system 1 also
starts.
Disallow on/off
via EMS
When the function is
disallowed, the EMS is not
allowed to start or shut down
the precision air conditioners.
No
Heat
Enable
indicates that the
electric heater will be started
when the ambient temperature
is lower than the certain
temperature range of the
temperature set point.
Disable
indicates that the electric
heater will not be started.
Enable
Heat mode
Sets the starting mode of the
electric heater.
Dehumid heat
Humid
Enable
indicates that the
electric humidifier will be
started when the ambient
humidity is lower than the
certain humidity range of the
humidity set point.
Disable
indicates that the electric
humidifier will not be started.
Enable
Humid mode
Sets the starting mode of the
humidifier.
Cooling and humid
Dehumid
Enable
indicates that the
dehumidification function will
be enabled when the ambient
humidity exceeds the certain
humidity range of the humidity
set point.
Disable
indicates
that the dehumidification
function will not be enabled.
Enable
Forced cooling
start temp
When the control type is air
return or hot aisle, set the
temperature for forcibly
starting the compressor when
the maximum temperature for
the cold aisle or supply air
surpasses this value.
25.0°C
Cooling off delay Sets the time delay for cooling
when the ambient temperature
reaches the lowest temperature
based on the
Temp set point
.
180s