Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
63
Menu
Parameter
Description
Default Value
Min dehumid
start temp
Sets the lower required
temperature limit for enabling
the dehumidification function.
–10%
Max dehumid
start temp
Sets the upper required
temperature limit for enabling
the dehumidification function.
50%
Min dehumid
close temp
Sets the lower required
temperature limit for disabling
the dehumidification function.
–100%
Max dehumid
close temp
Sets the upper required
temperature limit for disabling
the dehumidification function.
100%
Dehumid heat
start temp
Sets the upper required
temperature limit for starting
the electric heater during
dehumidification.
–50%
Low-temp heat
start temp
Sets the upper required
temperature limit for starting
the electric heater at low
temperature.
–100%
Max dehumid
runtime
Sets the dehumidification
duration for a precision air
conditioner in automatic mode.
60 min
Dew-point/sup-w
ater TD for
dehumid
Sets the minimum temperature
difference between the
ambient dew-point
temperature and supply water
temperature for enabling the
dehumanization.
5.0°C
Anti-cond
protection
Sets whether to enable
anti-condensation protection
(if disabled, no
anti-condensation protection
will be generated even when
protection conditions are met).
Enable
Anti-cond temp
diff
When the supply air
temperature is less than the
sum of the dew-point
temperature and
Anti-cond
temp diff
, the
anti-condensation protection
function is enabled.
You are not recommended to
change the value.
–2.0°C
Anti-cond delay
Sets the time delay for
20 min