Advanced Cooling Controller
User Manual
3 Power-on Commissioning
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
11
3.2.4 Setting Humidity Values
Context
The content in this section applies only to the NetCol8000-A.
To set
Humid control mode
, log in as the
Admin
or
Engineer
user. To set
Humid set
point
, log in as the
Admin
,
Engineer
, or
Operator
user.
Procedure
Step 1
On the home screen, choose
Settings
>
System Settings
>
Humidity Control
displayed.
Figure 3-5
Setting humidity values
Step 2
Set the parameters by referring to
You are not recommended to modify the parameters not listed in
Table 3-2
Parameter description
Parameter
Description
Configuration Principle
Humid control
mode
Two humidity
control modes
are available,
including relative
humidity control
and absolute
humidity control.
Set the parameter as required. You are recommended
to set the value to relative humidity.
Humid set
point
Indicates the
humidity
required in a
room or aisle.
The precision air
conditioner
performs the
humidification
and
The ACC controls the humidity based on the set
value. For example, if
Humid control type
is set to
Return-air
,
Humid control mode
set to
Relative
,
and
Humid set point
set to
50.0
, the ACC will
control the humidity around the return air vent of the
precision air conditioner to the humidity of 50% RH.