Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
61
Menu
Parameter
Description
Default Value
alarms that are generated
before the block. The LCD
displays active alarms and
the system implements
related protection actions.
Disallow
: Alarms are not
reported and no protection
actions are implemented.
Delay
Sets the delay time for
reporting alarms.
Not displayed
Threshold
Sets the alarm threshold for a
certain alarm.
Not displayed
Home
Screen
>
Settings
>
System
Settings
>
System
Control
Monitoring mode Sets the mode in which the
host computer software
monitors the precision air
conditioners.
Single mode
Unit startup
delay
Sets the time delay for starting
or re-powering on a precision
air conditioner, avoiding large
electric shocks when the
precision air conditioner is
started with other devices.
10s
Energy-saving
mode
Sets the fans to rotate at a low
speed when there is no
requirement.
Off
Alternate work
duration
Sets the alternative working
duration for the two modules
in a dual-module unit when the
cooling requirement is small.
100 h
Alternate work
mode
Alternate work: When
cooling is required, system
1 and system 2 take priority
to work in turn. When the
dual-system cooling time
difference reaches the
value of
Alternate work
duration
, the system with
shorter working time
begins to work first.
No. 1 system first: When
cooling is required, system
1 starts first. After the
cooling requirement
increases, system 2 also
starts.
No. 2 system first: When
cooling is required, system
Alternate work