Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
76
Menu
Parameter
Description
Default Value
Water supply
rate
After the humidification, the
water supply time is calculated
as follows: Water supply time
=
Water supply time
x
Water
supply rate
.
150%
Home
Screen
>
Settings
>
System
Settings
>
Drain
Device
Low float fall
pump off delay
When the low float rises, the
water pump begins to drain
water. When the low float
drops, the water pump will be
shut down after the time delay.
NetCol5000-A035
(025): 8s
NetCol5000-A020,
NetCol5000-C:
240s
High float fall
pump off delay
When the high float drops, the
water pump will be shut down
after the time delay.
NetCol5000-A035
(025): 25s
NetCol5000-A020,
NetCol5000-C:
300s
Low float rise
delay
Sets the time delay for
reporting an alarm and
shutting down the water pump
after the low float rises (if the
low float rises and do not drop
for a certain period, the float is
faulty or the water is not
properly drained).
NetCol5000-A035
(025): 300s
NetCol5000-A020,
NetCol5000-C:
600s
High float rise
delay
Sets the time delay for
reporting an alarm and
shutting down the water pump
after the high float rises (if the
high float rises and do not drop
for a certain period, the float is
faulty or the water is not
properly drained).
NetCol5000-A035
(025): 300s
NetCol5000-A020,
NetCol5000-C:
600s
Full water signal
delay
Indicates the time delay for
reporting a full water alarm
after the high float rises (the
system is shut down but the
water pump keeps running).
NetCol5000-A035
(025),
NetCol5000-A020
: 60s
NetCol5000-C:
180s
L-flt rise stdby
pump on delay
Indicates the time delay for
starting the standby pump after
the low float rises.
120s
Home
Screen
>
Settings
>
Quick
Settings
Language
Settings
Sets the interface language to
Chinese or English.
Consistent with the
current interface
language
Home
Date format
Sets the date display format
Consistent with the