NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
61
Position
Name
Address DIP Switch ID
1
2
3
4
5
6
temp/humid
Cold aisle 2
temp/humid
12
OFF
OFF
ON
ON
OFF
OFF
Cold aisle 3
temp/humid
13
ON
OFF
ON
ON
OFF
OFF
Cold aisle 4
temp/humid
14
OFF
ON
ON
ON
OFF
OFF
Cold aisle 5
temp/humid
15
ON
ON
ON
ON
OFF
OFF
Hot aisle
Hot aisle 1
temp/humid
21
ON
OFF
ON
OFF
ON
OFF
Hot aisle 2
temp/humid
22
OFF
ON
ON
OFF
ON
OFF
Hot aisle 3
temp/humid
23
ON
ON
ON
OFF
ON
OFF
Hot aisle 4
temp/humid
24
OFF
OFF
OFF
ON
ON
OFF
Hot aisle 5
temp/humid
25
ON
OFF
OFF
ON
ON
OFF
The default addresses of T/H sensors purchased from Huawei are 1.
Keep the last RS485_R toggle switch at OFF.
After the addresses are set, power on the device. On the display's home screen, choose
Settings
>
System Settings
>
T/H Sensor
and set the sensors in the aisles corresponding
to the addresses to
Enable
. Otherwise, the sensors will not work.
----End
3.12.7 (Optional) Installing a Differential Pressure Sensor
Procedure
Step 1
Secure the differential pressure sensor and the fasteners using M5 tapping screws, as shown in
step 1 in