6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
126
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
control board is
faulty.
Cold aisle
1
temp/humi
d sensor
comm
failed
Major
An
alarm is
triggere
d.
1.
The cables to the
temperature and
humidity sensor
are loose or
damaged.
2.
The DIP switch
of the
temperature and
humidity sensor
is set incorrectly.
3.
The temperature
and humidity
sensor is faulty.
4.
The
communications
port of the main
control board is
faulty.
1.
Check the cables
to the
temperature and
humidity sensor.
2.
Set the DIP
switch of the
temperature and
humidity sensor
correctly.
3.
Maintain or
replace the
temperature and
humidity sensor.
4.
Maintain or
replace the main
control board.
Cold aisle
2
temp/humi
d sensor
comm
failed
Major
An
alarm is
triggere
d.
1.
The cables to the
temperature and
humidity sensor
are loose or
damaged.
2.
The DIP switch
of the
temperature and
humidity sensor
is set incorrectly.
3.
The temperature
and humidity
sensor is faulty.
4.
The
communications
port of the main
control board is
faulty.
1.
Check the cables
to the
temperature and
humidity sensor.
2.
Set the DIP
switch of the
temperature and
humidity sensor
correctly.
3.
Maintain or
replace the
temperature and
humidity sensor.
4.
Maintain or
replace the main
control board.
Cold aisle
3
temp/humi
d sensor
comm
failed
Major
An
alarm is
triggere
d.
1.
The cables to the
temperature and
humidity sensor
are loose or
damaged.
2.
The DIP switch
of the
temperature and
humidity sensor
is set incorrectly.
3.
The temperature
1.
Check the cables
to the
temperature and
humidity sensor.
2.
Set the DIP
switch of the
temperature and
humidity sensor
correctly.
3.
Maintain or
replace the