NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
31
Figure 3-4
Connecting a water pump drainpipe
(1) Water pump port with an
outer diameter of 9.8 mm
(2) Hose
clamp
(3) Hose (inner diameter of 9 mm; made
of EPDM or other materials)
The object shown in the dotted line box is the water pump port supplied with the smart cooling product.
Other parts are not provided and need to be purchased.
3.1.3.3 (Optional) Humidifier Water Inlet Pipe
The humidifier water inlet pipe can be connected using a hose or a rigid pipe.
shows how to connect the pipe.
Figure 3-5
Connecting a water inlet pipe
(1) Connector with inner screw
threads: G 1/2 inch, delivered with
the water inlet pipe for the smart
cooling product
(2) Rigid pipe conversion
adapter: G 1/2 inch; connected
to a rigid pipe with outer screw
threads
(3) Rigid pipe:
made of PP-R or
other materials
(4) Pagoda connector: G 1/2 inch;
connected to a pagoda connector
with outer screw threads
(5) Hose clamp
(6) Hose: made of
EPDM or other
materials