NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
152
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
wn.
Otherwi
se, all
the
parts
except
for
indoor
fans are
shut
down.
blocked or bent.
4.
While
configuring the
condensate water
pump, check its
cable
connections,
clear the foreign
matter in it, or
replace it.
5.
While
configuring the
high liquid level
sensor, check its
cable
connections,
clear the
obstacles, or
replace it.
A27f-02
Water
overflow
alarm
Critical
An
alarm is
triggere
d, and
the
smart
cooling
product
is shut
down if
the
overflo
w alarm
is set to
shutdo
wn.
Otherwi
se, all
the
parts
except
for
indoor
fans are
shut
down.
1.
There is water at
the detection
position of the
water overflow
sensor.
2.
The cables to the
water overflow
sensor are loose
or damaged.
3.
The water
overflow sensor
is faulty.
1.
Check and clear
the water.
2.
Check the cables
to the water
overflow sensor.
3.
Maintain or
replace the water
overflow sensor.
A280-01
Power
frequency
abnormal
Major
An
alarm is
triggere
d.
1.
The power
supply frequency
is below the
lower threshold.
2.
The SPD
1.
Check the power
supply
frequency, and
ensure that it is
within the