NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
143
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
humidity alarm
threshold is
inappropriate.
4.
The value
detected by the
temperature and
humidity sensor
is different from
the actual value.
4.
Calibrate or
replace the
temperature and
humidity
sensors.
A097-01
Supply-wa
ter high
temperatur
e alarm
Major
An
alarm is
triggere
d.
1.
The temperature
of chilled water
is higher than the
supply water
high temperature
alarm threshold.
2.
The supply water
high temperature
alarm threshold
is inappropriate.
3.
The supply and
return water
pipes are
reversely
installed.
4.
The supply and
return water
sensors are
reversely
installed.
5.
The supply water
temperature
displayed is
different from
the actual
temperature.
1.
Check the
temperature of
supplied chilled
water.
2.
Adjust the
supply water
high temperature
alarm threshold.
3.
Exchange the
positions of the
supply and return
water pipes.
4.
Exchange the
positions of the
supply and return
water sensors.
5.
Calibrate or
replace the
supply water
temperature
sensor.
A098-01
Supply-wa
ter low
temperatur
e alarm
Warnin
g
An
alarm is
triggere
d.
1.
The temperature
of chilled water
is lower than the
supply water low
temperature
alarm threshold.
2.
The supply water
low temperature
alarm threshold
is inappropriate.
3.
The supply water
temperature
displayed is
different from
1.
Check the
temperature of
supplied chilled
water.
2.
Adjust the
supply water low
temperature
alarm threshold.
3.
Calibrate or
replace the
supply water
temperature
sensor.