NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
157
Figure 6-1
Removing an air filter
Step 3
Install the spare air filter and secure the baffle plate.
Step 4
Close and lock the rear door.
Step 5
Choose
Maint
>
Performance Maint
on the home screen to access the
Performance Maint
screen. Then clear the air filter runtime.
----End
6.4.3 Replacing the Humidifier Pump
Prerequisites
The pump needs to be replaced.
A spare pump of the same model is available and functional.
Context
Recommended tools: flat-head screwdriver
Preparations: The device is only maintained from the rear door and is powered off.
Before removing the water pump, block the water inlet pipe and drainpipe of the water pump
to prevent water overflowing out of the water pan and water pipe.