NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
45
Figure 3-22
Water pump drainpipe
Step 3
Connect the water pump drainpipe to the external drainage system.
Step 4
Wrap the water pump drainpipe with thermal insulation foam.
----End
3.8.3 (Optional) Connecting the Humidifier Water Inlet Pipe
Context
A reducing valve must be installed if the inlet water pressure exceeds 0.7 MPa.
Appliance is intended to be permanently connected to the water mains and not connected
by a hose-set.
Procedure
Step 1
Straighten the water inlet pipe delivered with the smart cooling product, and route it from the
inside to the outside through the water inlet hole at the bottom of the smart cooling product.