3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
43
The external drainpipe must have a certain gradient (> 1:50), and no accumulated water is
allowed.
The entire drainpipe should be closely wrapped with thermal insulation foam.
The drainpipe can be secured along the door post using cable ties inside a cabinet.
The water pump drainpipe and the automatic drainpipe should not be connected together
to the external drainage system.
Procedure
Step 1
Remove the drainpipe plug.
Figure 3-20
Connecting an automatic drainpipe
Step 2
Install a pipe adapter and seal it with sealant.
Step 3
Connect the PPR water pipe using a heat gun and wrap the pipe with thermal insulation foam.
Step 4
Connect the drainpipe to the external drainage system.
----End
Follow-up Procedure
After installing the condensate pump drainpipe and automatic drainpipe, connect them to the
main pipe and bind them with a cable tie according to step 1 in
. Then wrap the
pipes with tape or use other materials to secure them, as shown by step 2 in