NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
44
Figure 3-21
Fastening pipes
3.8.2 (Optional) Connecting the Water Pump Drainpipe
Context
Do not bend pipes by a large angle when securing pipes. The water pump drainpipe needs
to be wrapped with thermal insulation foam and the water pump inlet pipe does not need
thermal insulation foam.
In the cabinet, fasten the pipe to vertical pillar of rear door with cable ties.
Procedure
Step 1
Use a Phillips screwdriver to loosen the screw on the connector of the water pump drainpipe
to loosen the hose clamp, and remove the plug of the drainpipe.
Step 2
Connect the hose, and use a Phillips screwdriver to re-tighten the screw on the water pump
drainpipe to secure the hose clamp.