NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
33
Figure 3-7
Pipe supports (unit: mm)
The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including the thermal
insulation foam).
Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away from each
bending point in turning sections.
3.1.3.6 Cables
The cable flame spread rating must be at least VB.
The following lists the cables and devices to be connected. When connecting cables, fit them
with protective hoses.
Table 3-4
Cables and switches required
Name
Specifications
Quantity Remarks
Power cable
Electronic|Electric Cable,
600 V/1000 V, ZA-RVV,
3 x 6 mm
2
, Black (3
Cores: Brown, Blue,
Yellow/Green), 46 A,
Outdoor Cable, CE
2 PCS
Optional; same cable
parameters for the active
and standby routes
Teamwork
networking and
monitoring cable
Signal cable, Shielded
straight-through cable, 10
m, MP8-II, CC4P0.5GY
(S), MP8-II, FTP
1 PCS
Optional
Fuse
Slow Blow Fuse, 250 V,
4 A, IEC Specification,
0.03 ohm, 38.7 A x A x
Sec, UL/CSA Approved
2 PCS
Standard configuration;
delivered with the
product
OT terminal
Naked Crimping
Terminal, OT, 6 mm
2
,
6 PCS
Standard configuration;
delivered with the