NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
125
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
temperatur
e alarm
g
triggere
d.
temperature and
humidity sensors
are located in
inappropriate
positions.
2.
The thermal load
power is low.
3.
The ambient
temperature is
below the lower
threshold.
4.
The low
temperature
alarm threshold
is inappropriate.
5.
The value
detected by the
temperature
sensor or
temperature and
humidity sensor
is different from
the actual value.
6.
The air filters are
blocked.
7.
The chilled water
valve is stuck or
faulty.
temperature
sensors or
temperature and
humidity
sensors.
Step2.Contact
Huawei technical
support.
2.
Measure the
ambient
temperature.
Check whether
other causes
exist if the alarm
persists in a long
time after
startup.
3.
Adjust the low
temperature
alarm threshold.
4.
Calibrate or
replace the
temperature
sensor or
temperature and
humidity sensor.
5.
Maintain or
replace the air
filters.
6.
Maintain or
replace the
chilled water
valve.
A007-01
Return air
2
temp/humi
d sensor
comm
failed
Major
An
alarm is
triggere
d.
1.
The cables to the
temperature and
humidity sensor
are loose or
damaged.
2.
The DIP switch
of the
temperature and
humidity sensor
is set incorrectly.
3.
The temperature
and humidity
sensor is faulty.
4.
The
communications
port of the main
1.
Check the cables
to the
temperature and
humidity sensor.
2.
Set the DIP
switch of the
temperature and
humidity sensor
correctly.
3.
Maintain or
replace the
temperature and
humidity sensor.
4.
Maintain or
replace the main
control board.