Item
Method
Check Standard
Troubleshooting
Cable trays
inside pre-
fab. modules
Check whether the
cable trays are
securely connected
without damage or
misshapen.
Cable trays are
properly installed, and
fasteners are secure.
Secure cable trays that have
become loose.
Cable trays, screws,
and nuts are free from
rust or corrosion.
Repaint corroded cable trays, or
replace damaged and seriously
corroded parts. For details, see the
installation guide for the
corresponding solution.
Cables
Check cable
connections.
Cables are securely
connected without
bare terminals.
Secure terminal connections, and
replace terminals that do not meet
requirements. For details, see the
installation guide for the
corresponding solution.
Check whether
cables are intact.
● Cable jackets are
free from damage
or cracks.
● No cable overheats
due to overload
and the loads are
within the rated
capacity of the
cables (the cables
works only a very
short time under
overload
situations).
● The bend radius of
cables meets
requirements.
● The cable armor is
intact.
Replace parts that do not meet
requirements.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
3 Routine Maintenance
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
50