3.6.2 Cooling System
Table 3-15 Semi-annual maintenance checklist for the cooling system
Item
Method
Check Standard
Troubleshooting
Monitorin
g
Export smart cooling
product logs, alarms,
temperature, humidity, the
operating status of the
compressor, fan, electric
heater, electric humidifier,
and water pump, and time
from the monitoring
system. View the historical
alarms generated in this
quarter and select the
most common five ones
(skip this step if no
monitoring system is
configured).
-
Rectify the fault or contact
Huawei technical support.
Electric
heater
The electric heater is
secure.
The electric heater
is securely installed.
Secure the electric heater and
switch.
Check that the electric
heater surfaces are not
eroded.
The electric heater
surface is not
corroded.
Replace the electric heater if its
surface is eroded.
Compone
nts inside
the
electric
control
box
(Remove
the
electric
control
box
before
maintaini
ng the
internal
compone
nts.)
Check that all circuit
breakers and fuses work
properly.
Switches and fuses
are working
properly.
Replace faulty circuit breakers
and fuses.
Check that the cable
connection is secure and
correct.
Cables are securely
connected.
Secure loose cables.
Check that the electrical
components, control
components, SPDs, and
voltage detection boards
are not dusty.
The components are
clean and free from
dust.
(Perform the operation with the
power off.) Use a brush or
compressed dry air to remove
dust from electrical components,
control components, and voltage
detection boards.
Check that the control
board, display panel, T/H
sensor, and surge
protection and voltage
detection board are not
aging on the surface.
All components are
normal and free
from signs of aging.
Replace the abnormal board.
Check that all contactors
work properly.
Contactors work
properly and
smoothly.
Replace abnormal components.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
3 Routine Maintenance
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
42