Figure 4-34 Removing the liquid level detector
Step 6 Install the new liquid level detector and connect the interconnection terminal of
the liquid level detector.
Step 7 Tighten screws, connect cables, install the water pan cover, and close the front
door.
----End
4.2.2.11 (Optional) Replacing the Condenser Pump
Prerequisites
●
The water pump needs to be replaced.
●
A spare water pump of the same model is available and functional.
●
Tools: flat-head screwdriver, socket wrench
●
Before removing the water pump, drain water from the water pan completely.
Context
The water pump can be maintained only from the front.
Procedure
Step 1 Tap Shutdown on the LCD home screen and turn off the smart cooling product
switch in the PDC.
NO TICE
Exercise caution because the NetCol5000-A is still energized when it is being shut
down over the LCD.
Step 2 Open the front door and disconnect the water pump power cable.
Step 3 Remove the four screws from the cover, remove the cover.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
4 Parts Replacement
Issue 01 (2021-04-20)