![Huawei FusionDC1000A Maintenance Manual Download Page 57](http://html.mh-extra.com/html/huawei/fusiondc1000a/fusiondc1000a_maintenance-manual_168032057.webp)
Device
Method
Check Standard
Maintenance Guide
ASD
Check the ASD
sampling pipes.
The supports and connectors
of the sampling pipes are
securely connected.
Replace damaged
sampling pipes, and
apply glue where pipes
are not well sealed.
Remove or block a
sampling pipe.
An alarm is generated.
See documents delivered
with the ASD.
Release smoke to the
furthest end of an
ASD sampling pipe.
The ASD generates an alarm
in 120s.
See documents delivered
with the ASD.
The ASD panel displays an
alarm.
See documents delivered
with the ASD.
Check the ASD
operation panel.
All indicators are normal.
See documents delivered
with the ASD.
Check whether the
backup power is
working properly,
and whether the ASD
restarts normally
after the mains
powered is
disconnected.
The backup power is working
properly, and the ASD restarts
normally after the mains
power is disconnected.
See documents delivered
with the ASD.
ASD power
supply
Check the power
indicator.
The power indicator turns on.
1. Check the power
cables.
2. Replace the ASD
power supply.
3.6.6 Other Systems
Table 3-19 Semi-annual maintenance checklist for other systems
Item
Method
Check Standard
Troubleshooting
Lights
Check whether the
lights can be
switched on
normally.
The lights turn on
normally.
1. If a light cannot be switched on,
check whether the light is
securely installed and in good
contact with the light base.
2. If a light is securely installed and
in good contact with the light
base but fails to turn on, replace
the light.
Ventilation
vent air filter
Check whether the
filter is blocked.
The air filter is not
blocked.
If an air filter is slightly blocked,
clean the air filter and reinstall it. If
more than 50% of the meshes are
blocked, replace the air filter.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
3 Routine Maintenance
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
49