![Huawei FusionDC1000A Maintenance Manual Download Page 45](http://html.mh-extra.com/html/huawei/fusiondc1000a/fusiondc1000a_maintenance-manual_168032045.webp)
Check Item
Operation
Check Standard
Troubleshooting
AC actuator
Power input
Input voltage: 90–240 V AC
Check the input power
cables if the input voltage
is abnormal.
Power output
Output voltage: 90–240 V AC
For details, contact Huawei
technical support.
PWR indicator
Steady on: The power supply is
normal.
Off: No power supply is available.
Check the input power
cables.
ALM indicator
Steady on: A fault alarm is raised.
Off: No fault alarm is raised.
Clear alarms by referring to
the ECC800-Pro documents.
RUN indicator
Off: The power supply is
abnormal.
Blinking at long intervals: The
device successfully registers with
the ECC800-Pro and the software
runs properly (the indicator blinks
at 0.5 Hz, on for 1s and then off
for 1s).
Blinking at short intervals: The
communication is disconnected or
the device fails to register with
the ECC800-Pro (the indicator
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
Blinking: The indicator blinks at
super short intervals for 0.5s
(blinking at 10 Hz, on for 0.05s
and then off for 0.05s) and then
turns off for 0.5s. The cycle lasts
for 10s.
Check the power supply.
If the RUN indicator blinks
at short intervals, check
whether the RF_Z antenna
of the ECC800-Pro is
normal and whether the
antenna is shielded. If so,
install the antenna in a
different position. If not,
replace the AC actuator.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
3 Routine Maintenance
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
37