NO TE
As a terminal resistor is connected to the last heat detector in the loop in parallel, remove
the terminal resistor from the faulty heat detector, and connect the resistor to the new heat
detector when you replace the heat detector.
Step 4 Remove the screws on the base using a Phillips screwdriver, and remove the base.
Step 5 Install the new base to the same position, and reconnect the cables.
Step 6 Insert the new heat detector into the base, and rotate it clockwise until it locks in.
Step 7 Switch on the input circuit breaker of the extinguishant control panel, and connect
the battery cables.
Step 8 Check whether the new heat detector is working properly.
NO TE
If the red indicator blinks once every 6s, the heat detector is working properly.
----End
4.5.3 Replacing Warning Signs (CE)
Prerequisites
A spare warning sign of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: Phillips screwdriver, protective gloves, step ladder
Materials: spare warning sign
Documents: fire extinguishing drawings and parameters
Skill requirement: fire engineer
NO TICE
Before replacing the warning signs, inform the related administrative departments
of the temporary downtime of the fire extinguishing system. After the
replacement, inform the administration department that the system has become
operational.
Procedure
Step 1 Disconnect the battery cables, and switch off the input circuit breaker of the
extinguishant control panel.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
4 Parts Replacement
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
148