Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
64
―
HD3L Series Controller User Manual
Ref. Code
Function Description
Setting Range [Default]
F15.11
Set parameter 4 of stop status
0 - 32 [26]
F15.12
Set parameter 5 of stop status
0 - 32 [27]
F15.13
Set parameter 6 of stop status
0 - 32 [0]
The keypad displays parameters which is the run status (F15.02 - F15.07) and stop status (F15.08 - F15.13).
•
It can be cycling displayed by
key on the keypad.
•
Each content of display parameter can be set corresponding to 32 statuses.
•
For instance: when set F15.08 = 7, the stop parameter is setting RPM at initial power on.
0:
Unused.
1: Rated current of HD3L.
2: Controller status. Refer to d00.06.
3: Operate channel.
4: Setting speed.
5: Setting speed (after Acc / Dec).
6: Output frequency.
7: Setting RPM.
8: Running RPM.
9: Unused.
10: Output voltage.
11: Output current.
12: Output torque.
13: Output power.
14: DC bus voltage.
15: AI1 voltage.
16: AI1 voltage (after calculating).
17: AI2 voltage.
18: AI2 voltage (after calculating).
19: AI3 voltage.
20: AI3 voltage (after calculating).
21: AI4 voltage.
22: AI4 voltage (after calculating).
23: AO1 output.
24: AO2 output.
25: Heatsink temperature.
26: Input terminal status.
•
Bit0 - Bit11 correspond to DI1 - DI12.
27: Output terminal status.
•
Bit0 - Bit5 correspond to DO1, DO2 and RLY1 -
RLY4.
28: MODBUS status.
29: Total time at power on (hour).
30: Total running time (hour).
31: Unused.
32: Unused.
6.2.14
F16: Function-boost Parameters
Ref. Code
Function Description
Setting Range [Default]
F16.00
Zero-speed running signal delay time
0.00 - 10.00 [0.30s]
Defines the delay time of HD3L from zero-speed run status to zero-speed run signal output.
F16.01
Zero-speed signal delay time
0.00 - 10.00 [0.30s]
Defines the delay time of HD3Lfrom zero-speed status to zero-speed signal output.
F16.02
Current keep time after stop
0 - 9999 [0ms]
To eliminate the current noise of motor at stop, when the brake finished, the cut-off run signal will reduce the
current to zero after the time of F16.02.
F16.03 Fan
control
0 - 2 [0]
Defines the fan control mode. If there is overheat protection, the fan will run all the time.
0: Auto stop.
•
The fan runs all the time when HD3L is in run status. After HD3L stops for the time of F16.04, the fan
continues running if overheat protection is activated.
1: Immediately stop.
•
The fan runs all the time when HD3L is in running status, but stops when HD3L stops.
2: Run when power on.
•
The fan runs continuously after HD3L is switched on.