Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
62
―
HD3L Series Controller User Manual
Ref. Code
Function Description
Setting Range [Default]
F13.16 AO1
function
0 - 9 [0]
F13.17 AO2
function
0 - 9 [0]
0:
Unused.
1: Running speed (0 - max. output speed).
2: Setting speed (0 - max. output speed).
3: Output current (0 - twice rated current of HD3L).
4: Output voltage (0 - 1.2 times rated voltage of HD3L).
5: Bus voltage (0 - 2.2 times rated voltage of HD3L).
6: AI1 input (0 - 10V).
7: AI2 input (-10 - +10V/0 - 20mA).
8: AI3 input (-10 - +10V/0 - 20mA).
9: AI4 input (-10 - +10V/0 - 20mA).
Note:
1. At up, up limit of No. 1 and No. 2 function is corresponding to 10V, while down limit is corresponding to 5V;
2. At down, up limit of No. 1 and No. 2 function is corresponding to 0V, while down limit is corresponding to 5V;
3. Up limit of No. 3 - 5 functions is corresponding to max. output voltage 10V;
4. When the negative voltage of No. 7 - 9 function inputs, the AO will output its absolute value.
F13.18
AO1 bias
-100.0 - 100.0 [0.0%]
F13.19 AO1
gain
0.0 - 200.0 [100.0%]
The proportional relation of output can be adjusted by output gain, as shown in the figure below.
•
The formula is: AO1 actual output = F13.19 × Value before calcu F13.18.
F13.20
AO2 bias
-100.0 - 100.0 [0.0%]
F13.21 AO2
gain
0.0 - 200.0 [100.0%]
Refer to F13.18 and F13.19.
Value after
calculating (V)
0
5
10
100%
Value before
calculating (V)
F13.19=200%
F13.19=100%
Analogue output and gain
Value after
calculating (V)
0
10
100%
50%
Value before
calculating (V)
F13.18=50%
F13.18=0
Analogue output and bias