Chapter 4 Electrical Installation
Shenzhen Hpmont Technology Co., Ltd.
―
16
―
HD3L Series Controller User Manual
Table 4-2 HD3L I/O wiring specification
Model
MCCB
Contactor
Power Cable
Motor Cable
Ground Cable
Size
(A)
(A)
(mm
2
)
(mm
2
)
(mm
2
)
Single-phase / Three-phase power supply: 200 - 240V, 50/60Hz
HD3L-2D2P2
32 20 6
/
2.5
(1)
2.5
6 / 2.5
(1)
F2
HD3L-2D3P7
100 / 40
(1)
63
/32
(1)
16
/
6
(1)
4
16
/
6
(1)
F2
HD3L-2D5P5
125 / 63
(1)
100 / 40
(1)
35
/
10
(1)
6
16
/
10
(1)
F3
HD3L-2D7P5
160 / 63
(1)
100 / 40
(1)
35
/
16
(1)
10
16
F3
HD3L-2D011
200 / 100
(1)
125 / 63
(1)
50
/
25
(1)
16
25
/
16
(1)
F4
Three-phase power supply: 200 - 240V, 50/60Hz
HD3L-2T015
125 100 35
25
16
F5
HD3L-2T018
160 100 35
35
16
F5
HD3L-2T022
200 125 35
35
16
F6
HD3L-2T030
200 125 50
50
25
F6
Three-phase power supply: 380 - 460V, 50/60Hz
HD3L-4T2P2
16 10 1.5 0.75 2.5
F2
HD3L-4T3P7
25 16 2.5 2.5 2.5
F2
HD3L-4T5P5
32 25 4
4
4
F2
HD3L-4T7P5
40 32 6
6
6
F3
HD3L-4T011
63 40 10 10 10
F3
HD3L-4T015
63 40 16 16 16
F4
HD3L-4T018 100
63
16
25
16
F4
HD3L-4T022 100
63
25
25
16
F5
HD3L-4T030
125 100 35
35
16
F5
HD3L-4T037
160 100 35
35
16
F6
HD3L-4T045
200 125 35
35
16
F6
(1): Value before / is for single-phase model, value after / is for three-phase model.
16
4.2.2
Power terminal lug
Select the lug of power terminal according to the size of terminal, screw size and max. outer diameter
of lug. Refer to Table 4-3.
Take the round terminal as an example.
Table 4-3 Selection of power terminal lug
Size
F2
F3 / F4
F5
F6
Screw size
M4 M5 M6 M8
Tightening torque
(N. M)
1.2 - 1.5
2.5 - 3.0
4.0 - 5.0
9.0 - 10.0
Max. outer
diameter of lug d
(mm)
9.9 12 15.5 24
d