Troubleshooting 56
•
Rectifier input over current
•
Inverter output over current
•
Inverter fault
•
Heat sink over temperature
Action:
1.
If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general fault condition, see the HPE Power Manager
user guide available for download from the Hewlett Packard Enterprise website
http://www.hpe.com/info/rackandpower
2.
Verify that no blockage of airflow to the front bezel and rear panel exists.
General alarm condition
Action
:
1.
If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general alarm condition, see the HPE Power Manager
user guide available for download from the Hewlett Packard Enterprise website
http://www.hpe.com/info/rackandpower
2.
Check the batteries:
a.
Allow the UPS batteries to charge for 24 hours.
b.
If the Battery Fault LED
illuminates
, replace the batteries ("
UPS battery replacement procedure
" on
3.
Reduce the load:
a.
Power down the UPS ("
b.
Remove one or more load devices to reduce the power requirements.
c.
Wait at least 5 seconds and restart the UPS.
d.
If the condition persists, verify that the load devices are not defective.
4.
Allow the UPS to cool:
a.
Power down the UPS ("
b.
Clear vents and remove any heat sources.
c.
Verify that the airflow around the UPS is not restricted.
5.
Wait at least 5 minutes and restart the UPS.
6.
If the condition persists, contact a Hewlett Packard Enterprise authorized service representative.
Bypass is out of range
The input voltage is not within ±12 percent of nominal voltage.
The UPS is receiving utility power that might be unstable or in brownout conditions. The UPS continues to
supply power to the connected equipment. If conditions worsen, the UPS might switch to battery power.
Bypass out of range is only a status and does not keep the UPS from transferring to Auto-Bypass mode
(on page
Action:
1.
Check the input voltage and reconfigure the UPS ("
" on page
Summary of Contents for R/T3000 G2
Page 18: ...Installation 18 ...
Page 27: ...Installation 27 Attaching the ERM front bezel ...
Page 38: ...Installation 38 Installing the extension bars if included ...
Page 39: ...Installation 39 Connecting and securing the power cords ...
Page 71: ...Support and other resources 71 ...
Page 72: ...Support and other resources 72 ...
Page 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...