Installation 24
CAUTION:
Do not plug laser printers into the UPS output receptacles. The instantaneous
current drawn by this type of printer can overload the UPS.
Before connecting devices, verify that the UPS will not overload by checking that the ratings of the devices
do not exceed the UPS capacity. If the equipment rating is listed in amps, multiply the number of amps by
the selected output voltage to determine the VA.
After verifying that the UPS will not overload (depending on your model):
•
Connect the device power cords to the output receptacles on the rear panel of the UPS.
-or-
•
Connect devices to the output receptacles on the rear panel of the UPS using the IEC-to-IEC power
cords included with the UPS.
To provide additional receptacles:
•
Plug a PDU into the PDU output receptacle. The PDU output receptacle is part of load segment 1
and can be turned off and on using power protector software (on page
•
Plug an extension bar into any IEC-320-C19 receptacle to yield eight additional IEC-320-C13
receptacles.
Connecting the UPS cord retention clips
NOTE:
UPS appearance might vary depending on the specific unit installed.
Charging the UPS batteries
With the UPS in Standby mode, allow the batteries to charge before putting the UPS into service.
IMPORTANT:
Charge the batteries for at least 24 hours before supplying backup power to
devices. The batteries charge to:
•
80 percent of their capacity within 3 hours
•
100 percent of their capacity within 48 hours
Summary of Contents for R/T3000 G2
Page 18: ...Installation 18 ...
Page 27: ...Installation 27 Attaching the ERM front bezel ...
Page 38: ...Installation 38 Installing the extension bars if included ...
Page 39: ...Installation 39 Connecting and securing the power cords ...
Page 71: ...Support and other resources 71 ...
Page 72: ...Support and other resources 72 ...
Page 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...