Installation 21
WARNING:
To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11,
a UPS installed in a computer equipment room must be connected to a REPO circuit.
IMPORTANT:
The remote switch must be in the Off (open) position to enable power to the
output receptacles.
NOTE:
Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or
equivalent).
Separate wire pairs are attached to a single, normally-open contact in a parallel connection. Hewlett
Packard Enterprise recommends using different colors for the positive and negative wires.
If a connector becomes disconnected and is reconnected with reversed polarity, a REPO is initiated. To
avoid REPO port disconnect:
•
Minimize wire strain while connecting the REPO port.
•
Avoid allowing the wires to hang in the rear of the UPS.