Component identification 10
R/T3000 INT rear panel
Item Description
1
UPS option card
2
USB communications port
3
Serial communications port
4
Ground bonding screw
5
Load segment 1 and 2 (one IEC-320-C19 receptacle)
6
Load segment 1 (three IEC-320-C13 receptacles)
7
Load segment 2 (three IEC-320-C13 receptacles)
8
Cord retention clip attachment location
9
Cord retention clip attachment location
10
Cord retention clip attachment location
11
Ground bonding screw
12
REPO port
13
Input power receptacle (IEC-320-C20) for country-specific plug
attachment
REPO port
The UPS includes an isolated REPO port. When properly wired, the REPO feature enables the power at
the UPS output receptacles to be switched off from a remote location. To use this feature, the REPO port
must be connected to a remote, normally-open switch (not supplied). The REPO switch is used in
conjunction with a main disconnect device that removes the AC source from the input of the UPS. When
the switch is closed:
•
The REPO feature immediately powers down protected devices and does not utilize the orderly
shutdown procedure initiated by power management software.
•
The REPO feature shuts down UPS units operating under either utility or battery power.
NOTE:
If the UPS was operating on battery power when the remote switch was closed, no
power is available to the load devices until utility power is restored and the UPS has been
manually powered up.
Summary of Contents for R/T3000 G2
Page 18: ...Installation 18 ...
Page 27: ...Installation 27 Attaching the ERM front bezel ...
Page 38: ...Installation 38 Installing the extension bars if included ...
Page 39: ...Installation 39 Connecting and securing the power cords ...
Page 71: ...Support and other resources 71 ...
Page 72: ...Support and other resources 72 ...
Page 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...