Troubleshooting 58
•
If the condition occurred while reconnecting a disconnected REPO port, then verify the polarity of the
REPO connector pins.
For more information about REPO ports, see "Connecting the REPO port (on page
)."
Site wiring condition
Action
: Contact a qualified electrician to be sure that:
•
The line and neutral wires are not reversed in the wall outlet.
•
A ground wire connection does not exist.
Overload condition
All the load LEDs are illuminated.
Action
:
1.
Power down the UPS ("
2.
Remove one or more load devices to reduce the power requirements.
3.
Wait at least 5 seconds and restart the UPS.
4.
If the condition persists, verify that the load devices are not defective.
Checksum failure error
A Checksum failure error occurs when executing a bad load sequence, or having an incorrect EEPROM
map while loading software through the serial or USB port.
Action:
1.
Rerun the firmware upgrade.
2.
If the condition persists, contact a Hewlett Packard Enterprise authorized service representative.
UPS does not start
Action
:
1.
Be sure that the power cord is plugged in to a utility power receptacle.
2.
Check the power source at the utility power receptacle.
Low battery shutdowns
Ungraceful shutdown of attached servers occurs when the UPS is in a low battery condition.
Action
:
1.
Verify that the power management software is not delaying the shutdown of attached servers when
the UPS is in a low battery condition.
2.
Allow the UPS batteries to charge for 24 hours.
3.
If the Battery Fault LED
illuminates
UPS battery replacement procedure
" on page
Summary of Contents for R/T3000 G2
Page 18: ...Installation 18 ...
Page 27: ...Installation 27 Attaching the ERM front bezel ...
Page 38: ...Installation 38 Installing the extension bars if included ...
Page 39: ...Installation 39 Connecting and securing the power cords ...
Page 71: ...Support and other resources 71 ...
Page 72: ...Support and other resources 72 ...
Page 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...