Specifications 62
High-voltage UPS battery runtimes
Load, percent
Estimated battery
runtime
Runtime with one ERM
Runtime with two ERMs
20
40 minutes
125 minutes
225 minutes
50
12 minutes
50 minutes
89 minutes
80
6 minutes
30 minutes
54 minutes
100
4 minutes
24 minutes
43 minutes
Low-voltage UPS battery runtimes
Load, percent
Estimated battery
runtime
Runtime with one ERM
Runtime with two ERMs
20
45 minutes
142 minutes
256 minutes
50
15.5 minutes
55 minutes
99 minutes
80
7 minutes
34 minutes
60 minutes
100
5 minutes
26 minutes
47 minutes
Environmental specifications
Feature
Specification
Operating temperature 10°C to 40°C (50°F to 104°F); UL-tested at 25°C
(77°F)
Nonoperating
temperature
-15°C to 40°C (-5°F to 104°F)
Relative humidity
20% to 80%; noncondensing
Operating altitude
Up to 3,000 m (9,842 ft) above sea level
Nonoperating altitude
15,000 m (49,212 ft) above sea level
Audible noise
Less than 45 dBA, normal operation
Less than 50 dBA, on battery power
REPO port specifications
The REPO port meets the requirements of NFPA 70 and NEC Articles 645-10 and 645-11 for a
Disconnecting Means.
Summary of Contents for R/T3000 G2
Page 18: ...Installation 18 ...
Page 27: ...Installation 27 Attaching the ERM front bezel ...
Page 38: ...Installation 38 Installing the extension bars if included ...
Page 39: ...Installation 39 Connecting and securing the power cords ...
Page 71: ...Support and other resources 71 ...
Page 72: ...Support and other resources 72 ...
Page 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...