Specifications 61
UPS model
Load segment Output receptacles
—
—
1 x IEC-320-C19
R/T3000 INTL
1
3 x IEC-320-C13
—
—
1 x IEC-320-C19
—
2
3 x IEC-320-C13
—
—
1 x IEC-320-C19
Power protection specifications
UPS model
VA
Nominal power
rating (W)
Nominal voltage
setting
R/T3000 NA/JPN 2880 /
2400
2700 / 2250
120/100
R/T3000h NA/JPN 3300
3000
204
R/T3000 INTL
3300
3000
230
Output tolerance specifications
Source of power
Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
Battery power
±5% of nominal output voltage rating
Output feature specifications
Feature
Specification
Online efficiency
94% nominal input voltage
Voltage wave shape
Sine wave; 5% THD with typical PFC load
Surge suppression
300J via MOVs
Noise filtering
EN 55022 line filter for normal and common mode
use
Battery specifications
Feature
Specification
Type
12 V, 5 AH, sealed, maintenance-free, rechargeable, valve
regulated lead-acid batteries with a 3-5 year service life at 25
°
C
(77
°
F).
Voltage
The battery modules have a battery string voltage of 120 V.
Charging
Complete charge takes no more than 48 hours. After
approximately 3 hours, the batteries reach 80% charge at
default nominal utility voltage and no load.
Summary of Contents for R/T3000 G2
Page 18: ...Installation 18 ...
Page 27: ...Installation 27 Attaching the ERM front bezel ...
Page 38: ...Installation 38 Installing the extension bars if included ...
Page 39: ...Installation 39 Connecting and securing the power cords ...
Page 71: ...Support and other resources 71 ...
Page 72: ...Support and other resources 72 ...
Page 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...