Maintenance 48
To replace the components, reverse the removal procedure.
IMPORTANT:
Charge the batteries for at least 24 hours before supplying backup power to
devices. The batteries charge to:
•
80 percent of their capacity within 3 hours
•
100 percent of their capacity within 48 hours
Testing the new battery module
After installing the new battery module, press the Test/Alarm Reset button to initiate a self-test ("
IMPORTANT:
The UPS does not execute a self-test until the batteries are 90 percent
charged.
IMPORTANT:
Charge the batteries for at least 24 hours before supplying backup power to
devices. The batteries charge to:
•
80 percent of their capacity within 3 hours
•
100 percent of their capacity within 48 hours
If the installation has been successful, the Battery Fault LED is not illuminated. If the installation has not
been successful, the Battery Fault LED illuminates. If this occurs, repeat the UPS battery replacement
), and check the battery terminal connections. If the Battery Fault LED is still
illuminated, see "LED and audible alarm troubleshooting ("
" on page
)."
For the location of buttons, see "UPS front panel controls (on page
)."
For the location of LEDs, see "UPS front panel LED indicators (on page
)."
Replacing the UPS
To remove the UPS:
1.
Power down all attached load devices.
2.
Power down the UPS ("
3.
Switch the circuit breaker for any attached ERMs to the Off position.
Summary of Contents for R/T3000 G2
Page 18: ...Installation 18 ...
Page 27: ...Installation 27 Attaching the ERM front bezel ...
Page 38: ...Installation 38 Installing the extension bars if included ...
Page 39: ...Installation 39 Connecting and securing the power cords ...
Page 71: ...Support and other resources 71 ...
Page 72: ...Support and other resources 72 ...
Page 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...