Maintenance 47
Obtaining new batteries
New batteries might be required within 30 to 60 days when the Battery Fault LED illuminates. Obtain
spare batteries for the UPS when this occurs.
Spare battery modules are available for this UPS. The UPS spare battery kit part number is 517703-001.
CAUTION:
Because of the short shelf life of the batteries, avoid storing a battery spare as a
backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep
these batteries charged while in storage is implemented.
UPS battery replacement procedure
WARNING:
To prevent personal injury from electric shock or damage to the equipment,
remove the battery lead labels, and verify that the ERM circuit breakers are in the Off position.
This component is hot-swappable and can be replaced without powering down the UPS.
1.
(optional) To replace the component with the UPS powered down, refer to "Powering down the UPS
(on page
)."
CAUTION:
When hot-swapping batteries, the UPS is not protected in the event of a utility
power failure.
2.
Remove the UPS front bezel ("
3.
Disconnect the battery leads.
4.
Remove the UPS battery bracket.
5.
Remove the UPS battery modules.
IMPORTANT:
Do not pull the battery leads when removing or installing the batteries.
Summary of Contents for R/T3000 G2
Page 18: ...Installation 18 ...
Page 27: ...Installation 27 Attaching the ERM front bezel ...
Page 38: ...Installation 38 Installing the extension bars if included ...
Page 39: ...Installation 39 Connecting and securing the power cords ...
Page 71: ...Support and other resources 71 ...
Page 72: ...Support and other resources 72 ...
Page 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...