PowerSure
™
PSP
Quick-Start Guide for 350-650VA; 120V
W
HAT
’
S
I
N
T
HE
B
OX
• Quick-Start guide
• PowerSure family user manual on CD (also at
www.liebert.com
)
• Warranty card
• MultiLink
™
software CD; MultiLink serial cable (M3LS9P9S), 10 ft. (3m)
• RJ-11 cord, 7 ft. (2.1 m); USB cable, 6 ft. (1.8m)
For more details, refer to the PowerSure user manual on CD.
Para una información más detallada, consulte el manual del usuario de la
familia PowerSure en el CD.
* Power ON/OFF/
Alarm Silence
* Fault Indicator
(Red/Green)
* Utility Indicator
(Green)
* Battery Indicator
(Green/Amber)
DIP switches **
*** USB port
*** DB-9 port
Site Wiring Fault *
Indicator (Red)
** Orange output
receptacles
(battery backup and
surge protection)
** Black output
receptacles
(surge protection only
)
6-ft. (1.8m)
power cord
Battery cover plate
(bottom of UPS)
Data Line ***
Protection
Connectors
For details, see:
* Controls and Indicators
** Installation
*** Communications
I
NSTALLATION
Read all safety, installation and operating instructions in the PowerSure family user manual on the included CD or
at
www.liebert.com
before operating the UPS. Adhere to all warnings on the unit and in the manual.
1. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area
of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive
contaminants. Maintain a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an ambi-
ent temperature range of 32°F to 104°F (0°C to 40°C).
2. Plug the PSP’s power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated,
refer to the
Troubleshooting
section.
3. Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other
office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black
receptacles, which provide surge protection only.
4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.
5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indi-
cator will illuminate (green).
6. Turn on connected equipment.
Plug this type of equipment into
black receptacles ONLY
Plug computers, monitors & network hubs
into orange receptacles
Inkjet printers
Scanners
Fax machines
C
OMMUNICATIONS
The PowerSure PSP will communicate with your computer in either of two ways: over its DB-9 port through Lie-
bert’s MultiLink
™
software or by USB through Microsoft
®
Windows
®
operating system features.
MultiLink supplies useful monitoring data, such as input voltage and battery level, and will perform an orderly shut-
down of the computer system. Microsoft Windows XP and 2000 operating system utilities supply UPS status infor-
mation and will perform an orderly computer shutdown. Check your computer’s OS features to determine whether
it has power management capability.
For MultiLink Serial Communications
• Connect the provided MultiLink serial cable to the DB-9 ports on the rear of the UPS and on the rear of your
computer.
• Install the MultiLink software—the software, installation instructions and the user manual are on the CD included
in the PowerSure PSP package.
For USB Communications (with operating system power management)
• Connect the USB cable provided with the UPS to the USB ports on the PSP and your computer. The PSP will
work automatically with the built-in power management software on Windows XP and 2000 or later.
• All USB models are compatible with Microsoft Windows 2000, Windows XP and Macintosh
®
OS 10.2 or later.
C
ONTROLS
AND
I
NDICATORS
This button controls output power to the connected
load and has three functions:
• Turns the PowerSure PSP ON
• Turns the PowerSure PSP OFF
• Silences PowerSure PSP alarms
TURN THE UPS ON:
Press and release the main ON/OFF
button to start the UPS. An audible alarm will sound briefly.
TURN THE UPS OFF:
When the PSP is ON, hold the main
ON/OFF button down for more than 2 seconds to shut it down.
An audible alarm will sound briefly.
SILENCE AN ALARM:
When a UPS alarm is active, press and
release the main ON/OFF button to silence the audible alarm
(Exceptions: low battery, overload and overtemperature). DO
NOT hold the button down for more than 2 seconds or the PSP
will shut down.
CHECK THE PSP’S CONDITION:
Three status indicators on
the front of the UPS illuminate to specify the status of the UPS
(see
Troubleshooting
section for details).
SITE WIRING FAULT INDICATOR (RED)
The Site Wiring Fault Indi-
cator on the rear panel, as
shown, illuminates red
when the UPS detects a
line-neutral reversal or a
poor neutral-ground. (See
Troubleshooting Chart
if
indicator is illuminated.)
TRANSFER VOLTAGE SELECTORS (DIP SWITCHES)
The two-position DIP switch control on the rear panel, shown
above, allows the operator to select the utility transfer voltage
at which the UPS will switch to battery power. The factory
default settings are 100VAC - 135VAC. DIP switch positions for
each voltage setting are:
DIP switch settings
Left
Right
Setting
↑
Up
↑
Up
100 - 135VAC (default)
↑
Up
↓
Down
100 - 145VAC
↓
Down
↑
Up
90 - 135VAC
↓
Down
↓
Down
90 - 145VAC
!
CAUTION
Never change the voltage settings while the UPS
is ON and powering connected loads. Change
DIP switches only when the UPS is OFF.
!
CAUTION
To ensure protection of the connected
equipment, the DIP switch settings should match
the nominal utility input voltage. DIP switch
settings not matching the nominal utility could
potentially damage connected equipment.
Fault Indicator
Green: Overload/
Overtemperature
Red:
UPS fault
Utility Indicator
Green: Normal operation
Battery Indicator
Green: On battery
Amber: Battery
warning
DIP Switches
Site Wiring
Fault
Indicator
(Red)
Rear of UPS
S
PECIFICATIONS
Model Number
PSP350MT-120
PSP500MT-120
PSP650MT-120
Power Rating VA/W
350VA/210W
500VA/300W
650VA/390W
DIMENSIONS: in. (mm)
Unit
W x D x H
3.7 x 9.5 x 8
(95 x 240 x 205)
3.7 x 9.5 x 8
(95 x 240 x 205)
3.7 x 9.5 x 8
(95 x 240 x 205)
Shipping
W x D x H
6.7 x 13.1 x 11.5
(171 x 332 x 293)
6.7 x 13.1 x 11.5
(171 x 332 x 293)
6.7 x 13.1 x 11.5
(171 x 332 x 293)
WEIGHT: lbs (kg)
Unit
10.2 (4.6)
10.2 (4.6)
10.2 (4.6)
Shipping
12.6 (5.7)
12.6 (5.7)
12.6 (5.7)
INPUT AC PARAMETERS
Surge Protection
570J
Rated Input Voltage
120VAC
Voltage Range Without
Battery Operation
90VAC - 145VAC, DIP switch selectable
(see
DIP switch settings
)
Frequency Range
46.5 - 63.5 Hz (±0.1 Hz)
Input Power Cord
6 ft. (1.8m) attached, w/ NEMA 5-15 P
OUTPUT AC PARAMETERS
Output Receptacles
(4) NEMA 5-15R (orange)
Battery surge protection;
(2) NEMA 5-15R (black)
Surge protection
Voltage (Battery mode)
120VAC ±8%
Output Current
2.9 A
4.2 A
5.4 A
Waveform (Battery mode)
Stepped Sinewave
Frequency
50 Hz or 60 Hz; auto sensing
Overload Warning
(Normal & Battery modes)
>100%
Overload Shutdown
>110%
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
QuantityxVoltagexRating
(1)x12Vx7Ah
(1)x12Vx7Ah
(1)x12Vx9Ah
Transfer Time
4 - 6 ms typical
Backup Time:
At 77°F (25°C), resistive loading, with fully charged batteries
Full Load
9 minutes
4 minutes
5 minutes
Half Load
24 minutes
17 minutes
14 minutes
Recharge Time
6 hours to 90% of rated capacity,
after full discharge into resistive load
ENVIRONMENTAL (ALL MODELS)
Operating
Temperature
+32°F to + 104°F
(0°C to +40°C)
Storage
Temperature
+5°F to +104°F
(-15°C to +40°C)
Relative
Humidity
0% to 95%,
non-condensing
Operating
Elevation
Up to 10,000 ft.
(3000m)
at 86°F (30°C)
without derating
Audible Noise
< 40 dBA, at 1
meter
AGENCY (ALL MODELS)
Safety
UL 1778, c-UL
Listed
Surge
ANSI C62.41,
Category A, Level 3
(IEEE 587,
Category A);
EN61000-4-5,
Level 3, Criteria A
ESD
EN61000-4-2,
Level 3, Criteria A
Susceptibility
EN61000-4-3,
Level 3, Criteria A
Electrical Fast
Transient/Burst
EN61000-4-4,
Level 4, Criteria A
Emissions
FCC Part 15,
Subpart B, Class B
Conducted
Immunity
EN61000-4-6,
Level 3, Criteria A
Harmonics
EN61000-3-2
Flicker
EN61000-3-3
Transportation ISTA Procedure 1A