PowerSure

 PSP

Quick-Start Guide for 350-650VA; 120V

W

HAT

S

 I

N

 T

HE

 B

OX

• Quick-Start guide
• PowerSure family user manual on CD (also at 

www.liebert.com

)

• Warranty card
• MultiLink

 software CD; MultiLink serial cable (M3LS9P9S), 10 ft. (3m)

• RJ-11 cord, 7 ft. (2.1 m); USB cable, 6 ft. (1.8m)

For more details, refer to the PowerSure user manual on CD.
Para una información más detallada, consulte el manual del usuario de la 

familia PowerSure en el CD.

* Power ON/OFF/

Alarm Silence

* Fault Indicator

(Red/Green)

* Utility Indicator

(Green)

* Battery Indicator

(Green/Amber)

DIP switches **

*** USB port

*** DB-9 port

Site Wiring Fault * 

Indicator (Red)

** Orange output 

receptacles

(battery backup and 

surge protection)

** Black output

receptacles

(surge protection only

)

6-ft. (1.8m) 

power cord

Battery cover plate 

(bottom of UPS)

Data Line ***

Protection

Connectors

For details, see:

* Controls and Indicators

** Installation

*** Communications

I

NSTALLATION

Read all safety, installation and operating instructions in the PowerSure family user manual on the included CD or 

at 

www.liebert.com

 before operating the UPS. Adhere to all warnings on the unit and in the manual.

1. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area 

of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive 

contaminants. Maintain a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an ambi-

ent temperature range of 32°F to 104°F (0°C to 40°C).

2. Plug the PSP’s power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated, 

refer to the 

Troubleshooting

 section.

3. Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other 

office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black 

receptacles, which provide surge protection only.

4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.

5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indi-

cator will illuminate (green).

6. Turn on connected equipment.

Plug this type of equipment into 

black receptacles ONLY

Plug computers, monitors & network hubs 

into orange receptacles

Inkjet printers

Scanners

Fax machines

C

OMMUNICATIONS

The PowerSure PSP will communicate with your computer in either of two ways: over its DB-9 port through Lie-

bert’s MultiLink

 software or by USB through Microsoft

®

 Windows

®

 operating system features. 

MultiLink supplies useful monitoring data, such as input voltage and battery level, and will perform an orderly shut-

down of the computer system. Microsoft Windows XP and 2000 operating system utilities supply UPS status infor-

mation and will perform an orderly computer shutdown. Check your computer’s OS features to determine whether 

it has power management capability.

For MultiLink Serial Communications

• Connect the provided MultiLink serial cable to the DB-9 ports on the rear of the UPS and on the rear of your 

computer.

• Install the MultiLink software—the software, installation instructions and the user manual are on the CD included 

in the PowerSure PSP package.

For USB Communications (with operating system power management)

• Connect the USB cable provided with the UPS to the USB ports on the PSP and your computer. The PSP will 

work automatically with the built-in power management software on Windows XP and 2000 or later.

• All USB models are compatible with Microsoft Windows 2000, Windows XP and Macintosh

®

 OS 10.2 or later.

C

ONTROLS

 

AND

 I

NDICATORS

This button controls output power to the connected 

load and has three functions:
• Turns the PowerSure PSP ON

• Turns the PowerSure PSP OFF

• Silences PowerSure PSP alarms

TURN THE UPS ON: 

Press and release the main ON/OFF 

button to start the UPS. An audible alarm will sound briefly.

TURN THE UPS OFF:

 When the PSP is ON, hold the main 

ON/OFF button down for more than 2 seconds to shut it down. 

An audible alarm will sound briefly.

SILENCE AN ALARM:

 When a UPS alarm is active, press and 

release the main ON/OFF button to silence the audible alarm 

(Exceptions: low battery, overload and overtemperature). DO 

NOT hold the button down for more than 2 seconds or the PSP 

will shut down.

CHECK THE PSP’S CONDITION:

 Three status indicators on 

the front of the UPS illuminate to specify the status of the UPS 

(see 

Troubleshooting

 section for details).

SITE WIRING FAULT INDICATOR (RED)

The Site Wiring Fault Indi-

cator on the rear panel, as 

shown, illuminates red 

when the UPS detects a 

line-neutral reversal or a 

poor neutral-ground. (See 

Troubleshooting Chart

 if 

indicator is illuminated.)

TRANSFER VOLTAGE SELECTORS (DIP SWITCHES)

The two-position DIP switch control on the rear panel, shown 

above, allows the operator to select the utility transfer voltage 

at which the UPS will switch to battery power. The factory 

default settings are 100VAC - 135VAC. DIP switch positions for 

each voltage setting are: 

DIP switch settings

Left

Right

Setting

 Up

 Up

100 - 135VAC (default)

 Up

 Down

100 - 145VAC

 Down

 Up

90 - 135VAC

 Down

 Down

90 - 145VAC

!

CAUTION

Never change the voltage settings while the UPS 

is ON and powering connected loads. Change 

DIP switches only when the UPS is OFF.

!

CAUTION

To ensure protection of the connected 

equipment, the DIP switch settings should match 

the nominal utility input voltage. DIP switch 

settings not matching the nominal utility could 

potentially damage connected equipment.

Fault Indicator

Green: Overload/

Overtemperature

Red:

UPS fault

Utility Indicator

Green: Normal operation

Battery Indicator

Green: On battery
Amber: Battery 

warning

DIP Switches

Site Wiring 

Fault

Indicator 

(Red)

Rear of UPS

S

PECIFICATIONS

 

Model Number

PSP350MT-120

PSP500MT-120

PSP650MT-120

Power Rating VA/W

350VA/210W

500VA/300W

650VA/390W

DIMENSIONS: in. (mm)

Unit 

W x D x H

3.7 x 9.5 x 8

(95 x 240 x 205)

3.7 x 9.5 x 8

(95 x 240 x 205)

3.7 x 9.5 x 8

(95 x 240 x 205)

Shipping

W x D x H

6.7 x 13.1 x 11.5

(171 x 332 x 293)

6.7 x 13.1 x 11.5

(171 x 332 x 293)

6.7 x 13.1 x 11.5

(171 x 332 x 293)

WEIGHT: lbs (kg)

Unit

10.2 (4.6)

10.2 (4.6)

10.2 (4.6)

Shipping

12.6 (5.7)

12.6 (5.7)

12.6 (5.7)

INPUT AC PARAMETERS

Surge Protection

570J

Rated Input Voltage

120VAC

Voltage Range Without 

Battery Operation

90VAC - 145VAC, DIP switch selectable 

(see 

DIP switch settings

)

Frequency Range

46.5 - 63.5 Hz (±0.1 Hz)

Input Power Cord

6 ft. (1.8m) attached, w/ NEMA 5-15 P

OUTPUT AC PARAMETERS

Output Receptacles

(4) NEMA 5-15R (orange) 

Battery  surge protection; 

(2) NEMA 5-15R (black) 

Surge protection

Voltage (Battery mode)

120VAC ±8%

Output Current

2.9 A

4.2 A

5.4 A

Waveform (Battery mode)

Stepped Sinewave

Frequency

50 Hz or 60 Hz; auto sensing

Overload Warning 

(Normal & Battery modes)

>100%

Overload Shutdown

>110%

BATTERY PARAMETERS

Type

Valve-regulated, nonspillable, lead acid

QuantityxVoltagexRating

(1)x12Vx7Ah

(1)x12Vx7Ah

(1)x12Vx9Ah

Transfer Time

4 - 6 ms typical

Backup Time:

At 77°F (25°C), resistive loading, with fully charged batteries

Full Load

9 minutes

4 minutes

5 minutes

Half Load

24 minutes

17 minutes

14 minutes

Recharge Time

6 hours to 90% of rated capacity, 

after full discharge into resistive load

ENVIRONMENTAL (ALL MODELS)

Operating 

Temperature

+32°F to + 104°F

(0°C to +40°C)

Storage 

Temperature

+5°F to +104°F 

(-15°C to +40°C)

Relative 

Humidity

0% to 95%, 

non-condensing

Operating 

Elevation

Up to 10,000 ft.

(3000m)

at 86°F (30°C)

without derating

Audible Noise

< 40 dBA, at 1 

meter

AGENCY (ALL MODELS)

Safety

UL 1778, c-UL 

Listed

Surge

ANSI C62.41, 

Category A, Level 3

(IEEE 587, 

Category A);

EN61000-4-5, 

Level 3, Criteria A

ESD

EN61000-4-2, 

Level 3, Criteria A

Susceptibility

EN61000-4-3, 

Level 3, Criteria A

Electrical Fast

Transient/Burst

EN61000-4-4, 

Level 4, Criteria A

Emissions

FCC Part 15, 

Subpart B, Class B

Conducted 

Immunity

EN61000-4-6, 

Level 3, Criteria A

Harmonics

EN61000-3-2

Flicker

EN61000-3-3

Transportation ISTA Procedure 1A