Total (BTU/hour)
Unit Heat
(BTU/hour)
Maximum
Unit Heat
(BTU/hour) Typical
Number Installed
Enclosure Type
692
399
DL380p Gen8
Networking CLIM, 5
copper ports (IP or
Telco)
716
419
DL380p Gen8
Networking CLIM, 3
copper ports/2 optical
ports (IP or Telco)
427
256
M8381-25 SAS disk
enclosure (no disks)
30
17
SAS 2.5 in. 10k rpm
disk drive
24
14
SAS 2.5 in. 15k rpm
disk drive
19.93
19.45
Solid state drive, 200
GB
68
68
Maintenance switch
(Ethernet)
1
392
358
Rack-mount system
console (NSCR210 or
NSCR212)
96
96
Rack-mount keyboard
and display
1
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug must
be connected to the extension bars on the right side of the modular cabinet.
Operating Temperature, Humidity, and Altitude
Maximum Rate of Change
per Hour
Recommended Range
1
Operating Range
1
Specification
50° to 95° F (10° to 35° C)
Temperature (rack-mounted
system console and
maintenance switch)
18° F (10° C) Repetitive
68° to 77° F (20° to 25° C)
36° F (20° C) Nonrepetitive
-
50° to 95° F (10° to 35° C)
Temperature (CLIMs, SAS
disk enclosure, blade
elements)
1.8° F (1° C) Repetitive
5.4° F (3° C) Nonrepetitive
6%, noncondensing
40% to 50%,
noncondensing
20% to 80%,
noncondensing
Humidity
-
-
0 to 10,000 feet (0 to 3,000
meters)
Altitude
2
1
Operating and recommended ranges refer to the ambient air temperature and humidity measured 19.7 in. (50 cm)
from the front of the air intake cooling vents.
2
For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet), subtract 1.5× F
(0.83× C) from the upper limit of the operating and recommended temperature ranges.
70
System Installation Specifications for NS2100 Systems