Table 3 North America/Japan Three-Phase Power Specifications
Modular PDU 3-phase
iPDU 3-phase
R12000 3-phase UPS
24 A
24 A
12 kW
Output Load
208V 3P Delta
208V 3P Delta
208V 3P Wye
Input Voltage
NEMA L15-30P
NEMA L15-30P
IEC309 560P9
Input Connector
N/A
N/A
208V 3P Delta
Output Voltage
6 x C19
6 x C19
2 x NEMA L15-30R
Output Connectors
(42 x C13)
(20 x C13)
UPS outputs are connected to the compatible PDU inputs.
Notes
Table 4 International Single-Phase Power Specifications
Modular PDU 1-phase
iPDU 1-phase
R5000 1-phase UPS
32 A
32 A
4500 W
Output Load
200 – 240 V
200 – 240 V
220 – 240 V
Input Voltage
IEC309 332P6
IEC309 332P6
IEC309 332P6
Input Connector
(32 A)
(32 A)
(32 A)
N/A
N/A
220 – 240 V
Output Voltage
4x C19
6 x C19
1 x IEC309 332R6
Output Connectors
(28 x C13)
(20 x C13)
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
Notes
Table 5 International Three-Phase Power Specifications
Modular PDU 3-phase
iPDU 3-phase
R12000 3-phase UPS
16 A/phase
16 A/phase
12 kW
Output Load
380-415V 3P Wye
380-415V 3P Wye
380-415V 3P Wye
Input Voltage
IEC309 516P6
IEC309 516P6
IEC309 532P6
Input Connector
(32 A)
(32 A)
(32 A)
AC Input Power for Modular Cabinets
59