voltage of AC power at the intended installation site for the system. For information on the PDUs
supported for an NS2100 system, see
“AC Input Power for Modular Cabinets” (page 58)
Uninterruptible Power Supply (UPS)
An NS2100 system can use the HPE model R5000 UPS for a single-phase power configuration
or the HPE model R12000/3 UPS for a three-phase power configuration. An extended run-time
module (ERM) can be combined with a UPS to extend battery time. For more information, see
“Uninterruptible Power Supply (UPS)” (page 40)
.
AC Input Power for Modular Cabinets
This subsection provides information about AC input power for NS2100 modular cabinets.
•
contains the single-phase power specifications for the power components
used in North America and Japan.
•
contains the single-phase power specifications for the power components
used in North America and Japan.
•
contains the single-phase power specifications for the power components
used in international installations.
•
contains the single-phase power specifications for the power components
used in international installations.
CAUTION:
Be sure the hardware configuration and resultant power loads of each cabinet
within the system do not exceed the capacity of the branch circuit according to applicable electrical
codes and regulations.
Select circuit breaker ratings according to local codes and any applicable regulations for the
circuit capacity. Note that circuit breaker ratings vary if your system includes an optional
rack-mounted UPS.
Table 2 North America/Japan Single-Phase Power Specifications
Modular PDU 1-phase
iPDU 1-phase
R5000 1-phase UPS
24 A
24 A
4500 W
Output Load
200 – 240 V
200 – 208 V
200 – 208 V
Input Voltage
NEMA L6-30P
NEMA L6-30P
NEMA L6-30P
Input Connector
N/A
N/A
200 – 208 V
Output Voltage
4 x C19
6 x C19
1 x L6-30R
Output Connectors
(28 x C13)
(20 x C13)
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
Notes
58
System Installation Specifications for NS2100 Systems