Circuit breakers must be adequately rated for inrush and operating currents.
Hewlett-Packard recommends magnetic-type circuit breakers, which are capable
of handling large inrush currents for short durations (10 to 12 cycles) and are
rated adequately for steady state currents.
Choosing PDUs
Peak power requirements and PDU capacity affect the number of disk systems
that can be installed in a rack. For example, to install more than four disk systems
in Hewlett-Packard Rack Systems/E (HP Models J1500A(1.96M),
J1501A(1.60M), or J1502 (1.25M)), you must upgrade to 19-inch PDUs.
Besides rack density, the following factors can help you choose PDUs:
■
Redundant power source. To connect redundant power supplies to separate
PDUs, install redundant PDUs.
■
Number of cords to the AC source. Using 30-amp PDRUs instead of 16-amp
PDUs reduces the number of cords to the wall.
■
Future needs. Installing surplus PDU capacity allows you to add disk system
units later.
■
Inrush margins. For installations that require four or more 16-amp PDUs,
Hewlett-Packard recommends HP 30-amp PDRUs (E7681A, E7682A) for
their inherent inrush protection.
■
On/Off switch capability. Some PDU/PDRU options support the use of a
single-point on/off switch. See
Figure 12
and
Figure 13
.
The following tables show how many and what kind of PDU/PDRUs are needed
to install one or more disk systems in an HP rack. Data assumes 220V AC
nominal power and redundant PDU/PDRUs. For nonredundant configurations,
divide the number of recommended PDU/PDRUs by 2.
Summary of Contents for StorageWorks 2300 - Disk System
Page 1: ...hp StorageWorks disk system 2300 Edition E0902 user s guide ...
Page 10: ...10 ...
Page 14: ...14 Product Description ...
Page 35: ...Installation 35 Installation 2 ...
Page 40: ...40 Installation ...
Page 41: ...Installation 41 Installation ...
Page 48: ...48 Installation ...
Page 58: ...58 Installation ...
Page 59: ...Installation 59 Installation 4 Install clipnuts as shown in Figure 28 ...
Page 76: ...76 Installation ...
Page 77: ...Installation 77 Installation ...
Page 83: ...Configuration 83 Configuration 3 ...
Page 86: ...86 Configuration ...
Page 94: ...94 Configuration ...
Page 95: ...Troubleshooting 95 Troubleshooting 4 ...
Page 108: ...108 Removal and Replacement ...
Page 132: ......
Page 134: ......
Page 140: ......
Page 150: ...150 Reference E VCCI Statement Japan Harmonics Conformance Japan F BCIQ EMC Statement Taiwan ...
Page 151: ...Reference 151 Reference G Declaration of Conformity ...
Page 158: ...158 ...