Specifications
Environmental specifications
Specification
Value
System Inlet Temperature, Standard Operating
Support
—
Operating
10°C to 35°C (50°F to 95°F)
Non-operating
-30°C to 60°C (-22°F to 140°F)
Relative humidity (non-condensing)
—
Operating
Minimum to be the higher (more moisture) of -12°C
(10.4°F) dew point or 8% relative humidity
Maximum to be 24°C (75.2°F) dew point or 90%
relative humidity
Non-operating
5 to 95% relative humidity (Rh), 38.7°C (101.7°F)
maximum wet bulb temperature, non-condensing.
Altitude
—
Operating
3050 m (10,000 ft)
This value may be limited by the type and number of
options installed. Maximum allowable altitude change
rate is 457 m/min (1500 ft/min).
Non-operating
9144 m (30,000 ft)
Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305.0 m (1.8°F per 1000 ft) to 3050 m
(10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper
limit and rate of change might be limited by the type and number of options installed. System performance during
standard operating support may be reduced if operating with a fan fault or above 30°C (86°F).
The approved hardware configurations for this system are listed on the
.
116
Specifications
Summary of Contents for ProLiant DL560 Gen10
Page 6: ...Warranty information 124 Regulatory information 125 Documentation feedback 125 6 Contents ...
Page 27: ...Customer self repair 27 ...
Page 28: ...28 Customer self repair ...
Page 29: ...Customer self repair 29 ...
Page 30: ...30 Customer self repair ...
Page 102: ...16 SFF backplanes Group C SAS cables 102 Cabling ...
Page 113: ...Quad slimline riser installed in the secondary PCIe riser cage Tertiary riser Cabling 113 ...