Installing the Plenum (if required)
If installing one of the following SAN switches
only
, you must install the plenum that
ships in the accessory kit with the rack mount hardware:
•
4/8 SAN Switch
•
4/16 SAN Switch
•
4/32B SAN Switch
To install the plenum:
1.
Place the device (with inner rails attached) on a flat surface, see
Figure 17
.
2.
Obtain the plenum and four 8-32 x .312 Phillips Pan-head SEMs screws from the
accessory kit.
3.
For each inner rail (
Left
and
Right
) use one screw hole marked
8
and one screw
hole marked
16
to attach the plenum.
CAUTION:
Verify that the open end of the plenum faces the rear of the switch. For example, when
installed properly you should see the plenum’s air vent holes on one side, and the front
panel of the switch on the other.
SAN Switch installation guide
49