WEBVISION™
95-7769—01
120
Mode
X
X
X
Startup Wait
Heat
Cool
Off
Disabled
Emergency Heat
Smoke Emergency
Freeze Protect
Manual
Factory Test
Fan Only
Monitor Switch
X
X
X
Off or On
Monitor1
X
X
X
Units=V
Precision=1
Min=-32.0
Max=32.0
Network Manual Occupancy
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Occupancy Sensor
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Occupancy Status Out
X
X
X
Off or On
Occupancy Time Clock
X
X
X
Default
Off
Low
Medium
High
On
Outdoor Enthalpy
X
X
X
Units=mA
Precision=1
Min=-256.0
Max=256.0
Outdoor Humidity
X
X
X
Units=%
Precision=1
Min=0.0
Max=127.5
Outdoor Temperature
X
X
X
Units=ºF
Precision=1
Min=-256.0
Max=256.0
Proof of Air Flow
X
X
X
Default
Off
Low
Medium
High
On
Return Air Enthalpy
X
X
X
Units=mA
Precision=1
Min=-256.0
Max=256.0
Return Air Humidity
X
X
X
Units=%
Precision=1
Min=0.0
Max=127.5
Table 77. CVAHU Application of Points. (Continued)
Point Name
Graphics Alarms Trends Commandable Internal Use
Valid Values