Outside Air Quality
X
X
X
Units=ppm
Precision=0
Min=0.0
Max=65535.0
Override
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Proof Of Air Flow
X
X
X
Default
Off
Low
Medium
High
On
Return Air Enthalpy
X
X
X
Units=mA
Precision=1
Min=-256.0
Max=256.0
Return Air Humidity
X
X
X
Units=%
Precision=1
Min=0.0
Max=127.5
Return Air Temperature
X
X
X
Units=ºF
Precision=1
Min=-256.0
Max=256.0
Scheduled Occupancy
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Sensor Occupancy
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Shutdown
X
X
X
False or True
Smoke Monitor
X
X
X
False or True
Space CO2
X
X
X
Units=ppm
Precision=0
Min=0.0
Max=65535.0
Space Temperature
X
X
X
Units=ºF
Precision=1
Min=-256.0
Max=256.0
Effective Setpoint
X
X
X
Units=ºF
Precision=1
Min=-256.0
Max=256.0
Window Open
X
X
X
Closed or Open
Table 85. UV Application of Points. (Continued)
Point Name
Graphics Alarms Trends
Commandable
Internal Use
Valid Values