Nvi Bypass _value
X
X
X
X
Units=%
Precision=1
Min=0.0
Max=100.0
Nvi Bypass _state
X
X
X
X
Off
On
Default
Nvi Man Occ _occupancy
X
X
X
X
Occupied
Unoccupied
Bypass
Standby
Default
Nvo A I Sensor _ai Val
X
X
X
Units=null
Precision=1
Min=-inf
Max=+inf
Nvo Remote Cmd _lev Percent
X
X
X
Units=%
Precision=1
Min=-163.8
Max=163.8
Nvo Dig Cmd Free _value
X
X
X
Units=%
Precision=1
Min=0.0
Max=100.0
Nvo Dig Cmd Free _state
X
X
X
Off
On
Default
Nvo Appl Mode _hvac Mode
X
X
X
Default
Auto
Heat
Morning Warmup
Cool
Night Purge
Pre-cool
Off
Test
Emergency Heat
Fan Only
Free Cool
Ice
Maximum Heat
Economy
Dehumidify
Calibrate
Emergency Cool
Emergency Steam
Max Cool
HVAC Load
No Load
Nvo Econ Enable _value
X
X
X
Units=%
Precision=1
Min=0.0
Max=100.0
Nvo Econ Enable _state
X
X
X
Off
On
Default
Table 91. XL15C Application of Points. (Continued)
Point Name
Graphics
Alarms Trends
Commandable
Internal Use
Valid Values