WEBVISION™
141
95-7769—01
Application Mode
X
X
X
X
Default
Auto
Heat
Morning Warmup
Cool
Night Purge
Pre-cool
Off
Test
Emergency Heat
Fan Only
Free Cool
Ice
Maximum Heat
Economy
Dehumidify
Calibrate
Emergency Cool
Emergency Steam
Max Cool
HVAC Load
No Load
Fan Speed Command
X
X
X
X
Off
Zero
Low
Medium
High
Auto
Manual Mode
X
X
X
X
Enable
Disable
Manual
Suppress Alarms
Unsuppress Alarms
Manual Occupancy
X
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Temporary Setpoint
X
X
X
X
Units=ºC
Precision=1
Min=10.0
Max=35.0
Auxiliary Economizer Out
X
X
X
Off or On
Bypass Timer
X
X
X
Units=min
Precision=0
Min=0.0
Max=65535.0
Calculated Outdoor Enthalpy
X
X
X
Units=BTU/lb
Precision=1
Min=-256.0
Max=256.0
Calculated Return Air Enthalpy
X
X
X
Units=BTU/lb
Precision=1
Min=-256.0
Max=256.0
Coil Freeze State
X
X
X
False or True
Cool Percent
X
X
X
Units=%
Precision=1
Min=-163.8
Max=163.8
Table 85. UV Application of Points. (Continued)
Point Name
Graphics Alarms Trends
Commandable
Internal Use
Valid Values