WEBVISION™
173
95-7769—01
Scheduled State
X
X
X
Occupied
Unoccupied
Bypass
Standby
Occ Null
Space Humidity
X
X
X
Units=%
Precision=1
Min=-163.8
Max=163.8
Space Temperature
X
X
X
Units=ºC
Precision=1
Min=-273.2
Max=327.7
Stages Active
X
X
X
Units=null
Precision=0
Min=0.0
Max=7.0
SubBase Type
X
X
X
sbNul
sbSubasenone
sbSubase1
sbSubase2
sbSubase3
sbSubase4
sbSubase5
sbSubase6
sbSubase7
sbSubase8
sbSubase9
sbSubase10
sbSubase11
sbSubase12
sbSubase13
sbSubase14
sbSubase15
sbSubase16
System Mode
X
X
X
Default
Auto
Heat
Morning Warmup
Cool
Night Purge
Pre-cool
Off
Test
Emergency Heat
Fan Only
Free Cool
Ice
Maximum Heat
Economy
Dehumidify
Calibrate
Emergency Cool
Emergency Steam
Max Cool
HVAC Load
No Load
Temporary Setpoint
X
X
X
Units=ºF
Precision=1
Min=-8.0
Max=7.9
Table 93. T7350 Application of Points. (Continued)
Point Name
Graphics Alarms Trends
Commandable
Internal Use
Valid Values