WEBVISION™
107
95-7769—01
Condensation State
nvoChcStatus
condensationState
EnumPoint
Cool Output
nvoUnitStatus
coolOutput
NumericPoint
Cool Temperature
nvoChcStatus
coolTemp
NumericPoint
DLC Shed
nvoChcStatus
dlcShed
EnumPoint
Economizer Output
nvoUnitStatus
econOutput
NumericPoint
Effective Occupancy
nvoChcStatus
effectOcc
EnumPoint
Effective Sensor Occupancy
nvoChcStatus
effSenOcc
EnumPoint
Effective Window Open
nvoChcStatus
effWindowOpen
EnumPoint
External Active
nvoChcStatus
externalActive
EnumPoint
Fan Feedback
nvoChcStatus
fanFeedback
EnumPoint
Fan Output
nvoUnitStatus
fanOutput
NumericPoint
Fan Stages Active
nvoChcStatus
fanStagesActive
EnumPoint
HW Override
nvoChcStatus
hwOverride
EnumPoint
HW Window Open
nvoChcStatus
hwWindowOpen
EnumPoint
Humidity
nvoChcStatus
humidity
NumericPoint
Manual Occupancy
nvoChcStatus
netManOcc
EnumPoint
Unit Status Mode
nvoUnitStatus
mode
EnumPoint
CHC Status Mode
nvoChcStatus
mode
EnumPoint
Output Position 1
nvoChcStatus
outputPosition1
NumericPoint
Output Position 2
nvoChcStatus
outputPosition0
NumericPoint
Primary Heat Output
nvoUnitStatus
heatOutputPrimary
NumericPoint
RO LED
nvoChcStatus
rOLed
EnumPoint
Reheat Active
nvoChcStatus
reheatActive
EnumPoint
Reset Bypass Time
nvoChcStatus
restBypassTime
NumericPoint
Scheduled Occupancy
nvoChcStatus
schedOcc
EnumPoint
Secondary Heat Output
nvoUnitStatus
heatOutputSecondary
NumericPoint
Sensor Occupancy
nvoChcStatus
hwSenOcc
EnumPoint
Space Temperature
nvoChcStatus
spaceTemp
NumericPoint
Terminal Load
nvoTerminalLoad
levPercent
NumericPoint
Table 74. CHC Point Details. (Continued)
Point Name
Network Variable
Field Name
Point Type
Table 75. CHC Application of Points.
Point Name
Graphics Alarms Trends Commandable Internal Use
Valid Values
Occupied Cool (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Cool (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Cool (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Occupied Heat (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0