6.4.6 How to configure the device to measure volume or mass
The device can be configured to measure volume or mass. You can set up a strapping table in the
conversion table in the device's Quick Setup
Quick Setup
Quick Setup
Quick Setup menu.
How to create a volume or mass table.
•
Go to Supervisor > Quick setup > Setup mode > Conversion
Supervisor > Quick setup > Setup mode > Conversion
Supervisor > Quick setup > Setup mode > Conversion
Supervisor > Quick setup > Setup mode > Conversion.
•
Complete all the steps in the set-up procedure.
The device creates a table of up to 50 pairs of data (level
–
volume or level
–
mass). The
reference point for the table is the silo bottom (as given in menu item C.1.2 Tank Height).
INFORMATION!
You can also create customized length and conversion units (free units) in the Conversion
Conversion
Conversion
Conversion setup
procedure.
INFORMATION!
When you create a table, get more conversion data for parts of the silo where there are:
•
Surfaces with curves.
•
Sudden changes in the cross section.
This will make volume measurement more accurate.
Figure 6-6: A plot of points for a volume or mass table
1
Silo with reference points
2
Silo model with plotted points
Summary of Contents for SmartLine RM60
Page 8: ...CONTENTS 8 www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US SMARTLINE RM60 FMCW ...
Page 76: ...6 OPERATION 76 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 86: ...7 SERVICE 86 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 126: ...10 APPENDIX 126 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 127: ...APPENDIX 10 127 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...