OPERATION
6
63
SMARTLINE® RM60 (FMCW)
www.honeywell.com/ps
34-VF-25-31 iss.4 GLO December 15 US
Data dependencies for the 20 mA settings of outputs 1 and 2
6.4 Further information on device configuration
6.4.1 Protection of the device settings
The Passwords
Passwords
Passwords
Passwords menu lets you change the supervisor password.
How to change the supervisor password
•
Go to Supervisor > Advanced setup > Device setup > Passwords > Supervisor
Supervisor > Advanced setup > Device setup > Passwords > Supervisor
Supervisor > Advanced setup > Device setup > Passwords > Supervisor
Supervisor > Advanced setup > Device setup > Passwords > Supervisor.
•
Type in the new 6-character password (push the 4 buttons in any sequence).
•
Type in the new 6-character password again.
i
If the second entry is not the same as the first, the device will display the error message
"Password mismatch". Push [>>>>] and[
] at the same time and type in the new 6-character
password again.
•
Push [>>>>] and [
] (Esc) at the same time to go back to the "save settings" window.
•
Select Save
Save
Save
Save and push [
^
^
^
^
].
i
The device will go back to operator mode.
6.4.2 Network configuration
The device uses HART
®
communication to send information to HART
®
-compatible equipment. It
can operate in either point-to-point or multidrop mode. The device will communicate in
multidrop mode if you change the HART
®
address of output 1.
Output function
Minimum value
Maximum value
Default
Level
>4 mA Setting for Level
Tank TBO + RO
1
Tank
TBO - BD
2
Volume
>4 mA Setting for Volume
Max. value in the volume table
Max. value in
the volume
table
Mass
>4 mA Setting for Mass
Max. value in the mass table
Max. value in
the mass table
Distance
>4 mA Setting for Distance
Tank TBO + RO
1
Tank
RO
3
Ullage Volume
>4 mA Setting for Ullage Volume
Max. value in the volume table
Max. value in
the volume
table
Ullage Mass
>4 mA Setting for Ullage Mass
Max. value in the mass table
Max. value in
the mass table
1
RO = Reference Offset (C1.10). TBO = Tank Bottom Offset (C.1.11).
2
BD = Blocking Distance (C.1.9). TBO = Tank Bottom Offset (C.1.11).
3
RO = Reference Offset (C1.10).
INFORMATION!
Make a note of the password and keep it in a safe place. If you lose the password, please speak
or write to your supplier.
INFORMATION!
For more data, refer to Networks on page 38
.
Summary of Contents for SmartLine RM60
Page 8: ...CONTENTS 8 www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US SMARTLINE RM60 FMCW ...
Page 76: ...6 OPERATION 76 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 86: ...7 SERVICE 86 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 126: ...10 APPENDIX 126 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 127: ...APPENDIX 10 127 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...